Standards
|
Housing material |
PBT |
|
Inflammability class according to UL 94 |
V0 |
|
Color |
gray |
|
Standards for air and creepage distances |
DIN VDE 0110-1 |
|
IEC 60664-1: 1992-10 |
|
|
IEC 61643-11 |
|
|
Surge voltage category |
III |
|
Pollution degree |
2 |
|
Degree of protection |
IP20 |
|
Mounting type |
DIN rail: 35 mm |
|
Design |
DIN rail module, two-section, divisible |
|
Number of positions |
1 |
|
Ambient temperature (operation) |
-40 °C ... 80 °C |
|
Direction of action |
N-PE |
|
Width |
35.80 mm |
|
Height |
70.00 mm |
|
Length |
95.80 mm |
|
Pitch unit |
2 Div. |
Protective circuit
|
IEC category |
I |
|
T1 |
|
|
EN type |
T1 |
|
Lightning protection class |
I /100kA |
|
Nominal voltage UN |
240 V AC (N-PE) |
|
Arrester rated voltage UC (N-PE) |
350 V AC |
|
UT (TOV-proof) |
1200 V (200 ms) |
|
Nominal frequency fN |
50 Hz (60 Hz) |
|
Ground conductor current IPE |
≤ 5 µA (ground conductor current IPE) |
|
Standby power consumption PC |
≤ 0.35 mW |
|
Nominal discharge surge current In (8/20) µs (N-PE) |
100 kA |
|
Lightning test current (10/350) µs, charge |
50 As |
|
Lightning test current (10/350) µs, specific energy |
2.50 MJ/Ω |
|
Lightning test current (10/350) µs, peak value limp |
100 kA |
|
Impulse operate voltage at 6 kV (1.2/50)µs (N-PE) |
≤ 1.5 kV |
|
Protection level UP (N-PE) |
≤ 1.5 kV |
|
Residual voltage (N-PE) |
≤ 1.5 kV (at In) |
|
≤ 1 kV (at 10 kA) |
|
|
≤ 0.9 kV (at 5 kA) |
|
|
≤ 0.8 kV (at 3 kA) |
|
|
Clamping voltage SVR (N-PE) |
≤ 1.5 kV |
|
Response time (N-PE) |
≤ 100 ns |
|
Short-circuit resistance IP with max. backup fuse (effective) |
25 kA |
|
Follow current quenching capacity If (N-PE) |
100 A |
Connection, protective circuit
|
Connection method |
Screw terminal blocks |
|
Connection type IN |
Biconnect screw terminal block |
|
Connection type OUT |
Biconnect screw terminal block |
|
Connection method |
Biconnect terminal block |
|
Screw thread |
M5 |
|
Tightening torque |
4.5 Nm |
|
Stripping length |
18 mm |
|
Conductor cross section stranded min. |
2.5 mm² |
|
Conductor cross section stranded max. |
25 mm² |
|
Conductor cross section solid min. |
2.5 mm² |
|
Conductor cross section solid max. |
35 mm² |
|
Conductor cross section AWG/kcmil min. |
13 |
|
Conductor cross section AWG/kcmil max |
2 |
Remote indicator contact
|
Connection name |
Remote fault indicator contact |
|
Switching function |
PDT contact |
|
Connection method |
Plug-in/screw connection via COMBICON |
|
Screw thread |
M2 |
|
Tightening torque |
0.25 Nm |
|
Stripping length |
7 mm |
|
Conductor cross section stranded min. |
0.14 mm² |
|
Conductor cross section stranded max. |
1.5 mm² |
|
Conductor cross section solid min. |
0.14 mm² |
|
Conductor cross section solid max. |
1.5 mm² |
|
Conductor cross section AWG/kcmil min. |
28 |
|
Conductor cross section AWG/kcmil max |
16 |
|
Maximum operating voltage Umax. AC |
250 V AC |
|
Maximum operating voltage Umax DC |
125 V DC |
|
Max. operating current Imax |
1 A AC (inductive) |
|
1 A AC (ohmic) |
|
|
30 mA DC (inductive) |
|
|
200 mA DC (ohmic) |
Standards
|
Standards/regulations |
IEC 61643-1 2005 |
|
EN 61643-11 2002 |
|
|
EN 61643-11/A11 2007 |
|
|
UL 1449 ed. 2 |