Честотен регулатор iC5 1ph 230V 0.4kW

  • Производител: LSIS CO
  • Каталожен номер: LS6600000100
  • Вътрешен номер: SV004iC5-1
  • Бранш: Енергетика
  • Цена: 212.70 лв. без ДДС
  • Ценова единица: 1
  • Промо
     
200V Class Motor Rating [HP] 0.5      
[kW] 0.4      
Output ratings Capacity[kVA] 0.95      
FLA[A] 2.5      
Output frequency 0 ~ 400Hz
Output voltage 3 Phasde200~230V
Input ratings Voltage Single phase 200 ~ 230 V (±10%)
FLA[A] 5.5 9.2 16 21.6
Frequency 50 ~ 60 Hz (± 5%)
Control Control method V/F control, Sersorless vector control
Frequency setting resolution Digital reference: 0.01Hz
Analog referency: 0.06Hz/60Hz
Frequency setting resolution Digital reference: 0.01Hz
Analog referency: 0.06Hz/60Hz
V/F ratio Linear, Square pattern, User V/F
Overload capacity 1 min at 150%, 30 sec at 200% (with inverse characteristic)
Torque boost Manual torque boost (0~15 adjustable), auto torque boost
Input signal Operation method Keypad / Terminal / Communications
Frequency setting Analog: 0~10V / 4~20mA, Digital: Keypad,
Communication: RS485 (Option)
Start signal Forward, Reverse
Multi-step accel/decal time 0.1~6000 sec. Max. 8 types available by multi-function terminal, Selectable accel/decel patterns : Linear, U and S
Emergency stop Interrupting the output of the drive.
Jog Jog operation
Fault reset Reset the fault when protective function is active
Output signal Operation status & fault output Frequency detection, Overload alarm, Stalling, Overvoltage, Undervoltage, Drive overheating, Run, Stop, Constant speed, Speed searching, Fault output ( Relay and Open collector output )
Indicator Choose one from output frequency, current, voltage and DC voltage.(Output voltage : 0~10V )
Operation function DC braking, Frequency limit, Frequency jump, Second function, Slip compensation, Reversing prevention, Auto restart, PID control
Protection functions Drive trip Overvoltage, Undervoltage, Overcurrent, Drive overtemperature, Motor overtemperature, I/O phase loss, I/O mis-wiring, Overload , External device fault 1.2, Loss of speed command, Hardware fault, Communication error, CPU error
Drive alarm Stall prevention, Overload alarm
Momentary power loss Less than 15 msec: keeping operation
More than 15 msec: auto restart available
Display Keypad Operation information Output frequency, current and voltage, Set frequency value, Operation speed, DC voltage
Trip information Display the trip cause when the protection function activates. Recent 5 faults records stored
Environment Ambient temperature -10 ~ 40℃
Storage temperature -20 ~ 65℃
Humidity 90 %RH max (No condensing)
Atmosphere No corrosive gas, flammable gas, oil mist or dust
Pressure 70 ~ 106k Pa